CP VH 40-1
Product information:
Overvoltage arrester type 2, Consisting of base element and protective plug with high-performance varistor, remote signalling contact, Mounting type: Mounting rail TS 35, 1-channel, Rated voltage: 230 VAC
Product number:
16003.2
GTIN (EAN):
4044211144500
Quantity:
General | |
---|---|
Packaging unit: | 1 |
Quantity unit: | PC |
Weight per piece (not including packaging): | 106.1 g |
Weight per piece (including packaging): | 117.4 g |
Unit of weight: | G |
Customs number: | 85354000 |
Country of origin: | CN |
Product description: | Overvoltage arresters |
Dimensions | |
---|---|
Length: | 100.6 mm |
Width: | 18 mm |
Height: | 70 mm |
Installation dimensions acc. to DIN 43880: | 1 Te |
Ratings | |
Rated voltage Un: | 230 / 400 - |
Rated discharge surge current In (8/20) µs: | 20 kA |
Rated frequency min.: | 50 Hz |
Rated frequency max.: | 60 Hz |
Short-circuit resistance Ip: | 25 kA |
Connection data | |
Connection principle: | Screw connection |
Wire cross-section single core (rigid), min.: | 4 mm² |
Wire cross-section single-core (rigid), max.: | 25 mm² |
Wire cross-section stranded, min.: | 4 mm² |
Wire cross-section stranded, max.: | 25 mm² |
Wire cross-section stranded with wire-end ferrules, min.: | 25 mm² |
Wire cross-section stranded with wire-end ferrules, max.: | 4 mm² |
Output data | |
Switching current, max. at 30 V DC: | 2 A |
Switching current, max. at 250 V AC: | 0.5 A |
Remote signalling: | Potential-free CO contact |
Remote signalling: Wire cross-section single-core (rigid), max.: | 1,5 mm² |
Materials | |
Insulation housing: | Thermoplastic |
Flammability class UL 94: | V-0 |
Working temperature, min.: | -40 °C |
Working temperature, max.: | 85 °C |
Further technical data | |
Protection class: | IP20 |
Response time tA: | <25 ns |
Max. continuous voltage Uc: | 280 V |
Discharge current Imax (8/20) µs, max.: | 40 kA |
Protection level Up: | <1,25 kV |
Residual voltage Ures (5 kA): | <0,5 kV |
Operating current Ic: | <1 mA |
Follow-on current If: | None |
Follow-on current extinguishing capacity Ifi: | Infinite |
TOV voltage Ut (L-N): | 340 V / 5 s |
Series fuse, max.: | 125 gL A |
Malfunction display: | Mechanical, red |
Type of mains network: | TNC, TNS |
Environmental Product Compliance | |
REACH Conform: | yes |
REACH Reference date: | 2024-06-27 |
REACH Candidate Substance Note: | No |
RoHS Conform: | yes |
Standards and regulations | |
---|---|
DIN EN 61643-11 (Germany): | Arrester type 2 |
EN 61643-11 (Europe): | Low voltage SPD - Class II test |
IEC 61643-1 (International): | Low voltage SPD - Class II test |
UL1449 ed.2 (USA): | Low voltage TVSS |
File | Language | Type | Size | Version |
---|---|---|---|---|
Installationsanleitung CP_VH_40.pdf | German, English | 0.13 MB | 9/30/18 |