STK 2 BG
Product information:
Fuse-disconnect terminal, Screw connection, Mounting type:Mounting rail TS 35/7.5 and TS 32, Rated cross-section: 4 mm², Width: 8 mm, Colour: Beige
Product number:
1078.2
GTIN (EAN):
4044211013745
Quantity:
General | |
---|---|
Packaging unit: | 100 |
Quantity unit: | PC |
Weight per piece (not including packaging): | 10.4 g |
Weight per piece (including packaging): | 11.14 g |
Unit of weight: | G |
Customs number: | 85369010 |
Country of origin: | CZ |
Prio-Article: | 1078.2 |
Product description: | Fuse-disconnect terminal |
Dimensions | |
---|---|
Length: | 51.4 mm |
Width: | 8 mm |
Height TS 35/7.5: | 43.5 mm |
Height TS 32: | 39 mm |
Ratings | |
Rated voltage (determined by the illuminated display and fuse being used): | 500 V |
Rated current (as fuse-disconnect terminal): | 6,3 A |
Rated cross-section: | 4 mm² |
Rated impulse voltage: | 4 kV |
Overvoltage category: | III |
Contamination degree: | 3 |
Connection data | |
Connection principle: | Screw connection |
Connection position: | Lateral |
Connections: | 2 / extraction lever |
Number of terminals per level: | 2 |
Number of levels: | 1 |
Wire cross-section single-core (rigid) / stranded, min.: | 0.2 mm² |
Wire cross-section single core (rigid)/stranded, max.: | 4 mm² |
Wire cross-section stranded, min.: | 0.2 mm² |
Wire cross-section stranded, max.: | 4 mm² |
Wire cross-section stranded with wire-end ferrules, min.: | 0.2 mm² |
Wire cross-section stranded with wire-end ferrules, max.: | 4 mm² |
Wire cross-section AWG, min.: | 22 |
Wire cross-section AWG, max.: | 12 |
Stripping length: | 9 mm |
Screw head: | Slotted |
Screw threading: | M 3 |
Tightening torque, min.: | 0.5 Nm |
Tightening torque, max.: | 1 Nm |
Materials | |
Insulation housing: | Polyamide 6.6 |
Flammability class UL 94: | V-2 |
Working temperature, min.: | -40 °C |
Working temperature, max.: | 105 °C |
Further technical data | |
Mounting type: | Mounting rail TS 35/7.5 and TS 32 |
Fuse size: | 5 x 20 / 5 x 25 mm |
Gauge plug acc. to EN 60 947-1: | A4 |
End plate required: | |
Voltage fuse: | 250 V |
Power loss in singular arrangement - overload and short-circuit protection, max.: | 1,6 / 6,3 W / A |
Power loss in compound arrangement - overload and short-circuit protection, max.: | 1,6 / 6,3 W / A |
Power loss in singular arrangement - only short-circuit protection, max.: | 4 / 6,3 W / A |
Power loss in compound arrangement - only short-circuit protection, max.: | 2,5 / 6,3 W / A |
Version of fuse holder: | Swivelling |
Version of fuse cartridge: | G fuse 5 x 20 / 5 x 25 |
Environmental Product Compliance | |
REACH Conform: | yes |
REACH Reference date: | 2024-01-23 |
REACH Candidate Substance Note: | No |
RoHS Conform: | yes |
CSA approval | |
---|---|
CSA approval: | C22.2 No 158 |
CSA approval granted: | |
CSA Usegroup C: rated voltage: | 500 V |
CSA Usegroup C: rated current: | 6,3 A |
CSA wire cross-section AWG, min.: | 22 |
CSA wire cross-section AWG, max.: | 12 |
CSA stripping length: | 9 mm |
CSA torque, max.: | 1 Nm |
CSA torque, min.: | 0.5 Nm |
CSAus approval | |
CSAus approval: | UL 1059 |
CSAus approval granted: | |
CSAus Usegroup C: rated voltage: | 500 V |
CSAus Usegroup C: rated current: | 6,3 A |
CSAus wire cross-section AWG, min.: | 22 |
CSAus wire cross-section AWG, max.: | 12 |
CSAus stripping length: | 9 mm |
CSAus torque, min.: | 0.5 Nm |
CSAus torque, max.: | 1 Nm |
KEMA KEUR approval | |
KEMA KEUR approval: | EN 60947-7-1:2009, EN 60947-7-3:2009 |
KEMA KEUR approval granted: | |
KEMA rated voltage: | 500 V |
KEMA voltage fuse, max.: | 250 V |
KEMA rated current: | 6,3 A |
KEMA rated impulse voltage: | 4 kV |
KEMA wire cross-section single core (rigid), min.: | 0.2 mm² |
KEMA wire cross-section single-core (rigid), max.: | 4 mm² |
KEMA wire cross-section stranded, min.: | 0.2 mm² |
KEMA wire cross-section stranded, max.: | 4 mm² |
KEMA torque, min.: | 0.5 Nm |
KEMA torque, max.: | 1 Nm |
KEMA fuse size: | 5 x 20 / 5 x 25 mm |
KEMA power loss in singular arrangement - overload and short-circuit protection, max.: | 1,6 / 6,3 W / A |
KEMA power loss in compound arrangement - overload and short-circuit protection, max.: | 1,6 / 6,3 W / A |
KEMA power loss in singular arrangement - only short-circuit protection, max.: | 4 / 6,3 W / A |
KEMA power loss in compound arrangement - only short-circuit protection, max.: | 2,5 / 6,3 W / A |
File | Language | Type | Size | Version |
---|---|---|---|---|
CAD_1078_STK_2 | STP | 1.29 MB | 9/29/18 | |
Operating instructions SIK STK STKD SK | German, English | 0.19 MB | 9/30/18 |
- End plate
- Insulated external cross-connector
- End stop
- Solid link
- Quick marking
- Screwdriver
- CONTA-CONNECT